Parameter settings
3066501_201910 WOLF GmbH | 63
7.2.20 HG39: Soft start time
In heating mode, the burner is run at a lower output for the set time after starting.
7.2.21 HG40:Systemconguration
The heat generator is matched to the system by selecting from 7 precongured system versions.
Parameter HG40 can only be viewed and congured with the BM-2 programming unit or the AM display
module directly on the control module of the heat generator. This parameter affects both the function of
the feed/heating circuit pump and input E2 (12.3 HG40: System conguration).
7.2.22 HG42: Header hysteresis
The header hysteresis regulates the header temperature within the set range by switching the heat
generator on and off.
TS cylinder:
The starting/stopping point for cylinder heating is reduced automatically by 2 K for stratication and in
order to avoid overheating. The software can detect when a TS cylinder is connected.
7.2.23 HG46: Excess boiler water temperature, header
H46 sets the excess temperature differential between the header temperature and the heat generator
temperature during header heating. The temperature of the heat generator continues to be limited by the
maximum boiler temperature (HG22).
7.2.24 HG47/49: CO
2
setting
CO
2
adjustments can be made for the heat exchangers to match the ue system by changing the fan
speed for burner operation - stage 1 (HG47) or burner operation - stage 2 (HG49).
7.2.25 HG56: Input E3
HG56 can be selected only if the "I/O module" expansion board is connected.
The ue gas damper function cannot be selected.
All other functions can be set as for HG13 (input E1).
7.2.26 HG57: Input E4
HG57 can be selected only if the "I/O module" expansion board is connected.
The ue gas damper function cannot be selected.
All other functions can be set as for HG13 (input E1).
7.2.27 HG58: Output A3
HG58 can be selected only if the "I/O module" expansion board is connected.
The ue gas damper function cannot be selected.
All other functions can be set as for HG14 (output A1).
7.2.28 HG59: Output A4
HG59 can be selected only if the "I/O module" expansion board is connected.
The ue gas damper function cannot be selected.
All other functions can be set as for HG14 (output A1).
7.2.29 HG60: Minimum burner hysteresis
Based on the maximum burner hysteresis (HG01), there is a linear reduction of the burner shutdown point
after the burner starts. After the hysteresis time (HG33), the burner switches off at the minimum burner
hysteresis (HG60).
Also see parameter HG01 diagram.