EasyManuals Logo

Woodward GCP-30 Series Configuration

Woodward GCP-30 Series
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #125 background imageLoading...
Page #125 background image
Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 125/174
Engine
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 287
Configure
engine YES
Configuration of the engine YES/NO
Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO ................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
Parameter 288
Aux.services
prerun 000s
Engine; auxiliary prerun (start preparation) 0 to 999 s
Prior to each starting sequence, a relay output (relay manager function 52) can be
enabled for this time (i.e. prelube pumps run). A message is displayed when the re-
lay output is enabled. This relay output is automatically enabled in MANUAL op-
eration mode. The relay output is present until the operation mode is changed.
CAUTION
This delay is ignored in the event of emergency power operation. The engine is
started immediately.
Parameter 289
Aux.services
postrun 000s
Engine; auxiliary postrun 0 to 999 s
The relay output (relay manager function 52) can be enabled for this time following
each engine cool down (i.e. operate a coolant pump). If the operation mode is
changed from MANUAL to STOP or to AUTOMATIC without an engine start re-
quest, the relay remains enabled for this postrun time and a message is displayed.
Parameter 290
Start-stop-logic
for ------------
Engine; start/stop sequence for ... DIESEL/GAS/EXTERNAL
DIESEL ....... Start/stop logic is performed for a diesel engine.
GAS ............. Start/stop logic is performed for a gas engine.
EXTERNAL External start/stop sequence (the start/stop sequence is disabled).

Table of Contents

Other manuals for Woodward GCP-30 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-30 Series and is the answer not in the manual?

Woodward GCP-30 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-30 Series
CategoryController
LanguageEnglish

Related product manuals