Counter / Real Time Clock
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 312
Configure
counters YES
Configuration of the counters YES/NO
Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO ................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
Maintenance Call
Parameter 313
Service interval
in 0000h
Counter; maintenance call 0 to 9,999 h
A maintenance interval can be specified with this parameter. After the engine has
been in operation for the number of hours configured here, a maintenance message
(class F1 alarm) is displayed. Following the acknowledgement of the message, the
counter is reset to this value.
Note
Entering "0" will disable the maintenance call.
NOTE
In order to reset the maintenance call prior to the configured time (maintenance call alarm not yet in-
itiated), perform the following procedure:
- Navigate to the display screen "Service in 000h" using the "Select" button.
- Press and hold the "Digit" button for 10 seconds.
- The new maintenance interval is displayed.
Operating Hours Counter
Parameter 314
Set oper.hours
counter 00000h
Counter; operating hours counter 0 to 65,000 h
This parameter can be used to specify the number of hours an engine has been in
operation. This permits the user to display the correct number of engine hours if
this controller is used on an older engine or this controller is to replace an older
controller.
Note: The operating hours counbter may only be accessed from code level 2 with
the RPQ Package.
NOTE
If the unit is equipped with option SC06, SC07, or SC08, and the MDEC or J1939 coupling is enabled as
well, the operating hours will be taken over from the engine control unit. Please refer to manual 37313
for further information.

Table of Contents

Other manuals for Woodward GCP-30 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-30 Series and is the answer not in the manual?

Woodward GCP-30 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-30 Series
CategoryController
LanguageEnglish

Related product manuals