NOTE
If a value is to be input in this parameter other than the factory default, the controller must be in code
level CS2. For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Set and store the desired operating hours
2. Step: Integrate the value which has been saved by ...
-- Terminate the configuration mode and switch to automatic mode
-- Display of the operating hours
-- Press and hold the "Digit" push-button for at least 5 seconds.
Rental Duty Time Counter (only RPQ Package)
The RPQ Rental Package provides an rental duty time counter with minute resolution (max. 9999:59h). It may be
accessed in every code level. This counter is an additional operating hours counter which may be used for charg-
ing the cost when renting the unit.
The rental duty time counter may be reset to 0 before utilization for example. In order to perform this, the unit
must be in code level 2, the rental duty time counter must be displayed, and then the Digit button must be pressed
for at least 5 s.
NOTE
The rental duty time counter cannot be used to count the actual operating hours because it may be re-
set independently from the operating hours counter.
Start Counter
Parameter 315
Set start
counter 00000
Counter; number of engine starts 0 to 32,000
The start counter is used to display how many times the engine has been started.
Following each starting attempt the start counter is increased by one. This permits
the user to display the correct number of starts if this controller is used on an older
engine, a starter is replaced, or this controller is to replace an older controller.
Only maintenance personnel should configure the start counter!
NOTE
If the engine start counter is to be changed from the factory default setting, the controller must be in
code level CS2. For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Set and store the desired number of starts
2. Step: Integrate the value which has been saved by ...
-- Terminate the configuration mode and switch to automatic mode
-- Display the number of engine starts
-- Press and hold the "Digit" push-button for at least 5 seconds