EasyManua.ls Logo

Woodward GCP-30 Series - Discrete Inputs

Woodward GCP-30 Series
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 105/174
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 224
Configure
dig.inputs YES
Configuration of discrete inputs YES/NO
Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES .............. The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor", "Di-
git" or "Select" push-buttons).
NO ................ The parameters in the next block are not displayed, cannot be mod-
ified and are therefore skipped.
NOTE
The discrete inputs can be used as alarm inputs or control inputs. If they were configured as alarm in-
puts (Parameter 230 to Parameter 238 are configured to "OFF") the parameters in "Alarm Inputs"
(p
age 106) are valid. If they have been configured as control inputs (Parameter 230 to Parameter 238
are co
nfigured to "ON") the parameters in "
Control Inputs" (page 108) are valid.

Table of Contents

Other manuals for Woodward GCP-30 Series

Related product manuals