Manual 37278B GCP-30 Series - Genset Control
Page 160/174 © Woodward
Appendix D.
List of Parameters
Unit number P/N _____________________________ Rev _______________________________
Version GCP-30 _______________________________________________________________
Project ______________________________________________________________________
Serial number S/N _______________ Date ______________________________
Parameter Setting range Default value Customer setting
Software version
- V x.xxxx - -
Enter code
0 to 9.999 XXXX
Direct para.
YES/NO NO Y N Y N
Generator number
1 to 14 1
Language
first/second first f s f s
Check event list
YES/NO NO Y N Y N
GENERATOR AND MAINS ENVIRONMENT CONFIGURATION
Configure measuring
YES/NO NO Y N Y N
B + X
Generator freq. f set
40.0 to 70.0 Hz 50.0 Hz
B + X
Rated system frequency
50.0 to 60.0 Hz 50.0 Hz
RPQ
Rated Frequency System 1
50.0 to 60.0 Hz 50.0 Hz
RPQ L
Setpoint Frequ. System 1
45.0 to 65.0 Hz 50.0 Hz
RPQ
Rated Frequency System 2
50.0 to 60.0 Hz 60.0 Hz
RPQ L
Setpoint Frequ. System 2
45.0 to 65.0 Hz 60.0 Hz
B + X
Gen.volt.transf. secondary
50 to 125/50 to 480 V 400 V
B + X
Gen.volt.transf. primary
0.05 to 65.0 kV 0.4 kV
B + X
Bus.volt.transf. secondary
50 to 125/50 to 480 V 400 V
B + X
Bus.volt.transf. primary
0.05 to 65.0 kV 0.4 kV
B + X
mains volt.trans. secondary
50 to 125/50 to 480 V 400 V
B + X
mains volt.trans primary
0.05 to 65.0 kV 0.4 kV
B + X
Gen.voltage U set
50 to 125/50 to 530 V 100/400 V
B + X
Rated voltage in system
50 to 125/50 to 480 V 100/400 V
RPQ
Rated Voltage System 1
50 to 500 V 400 V
RPQ
Setpoint Voltage System 1
50 to 530 V 400 V
RPQ L
CT generator System 1
10 to 7,000/{X} A 500/{X} A
RPQ L
Gen Rated curr. System 1
10 to 7,000 A 300 A
RPQ L
Gen rated power System 1
5 to 9,999 kW 200 kW
RPQ
Rated Voltage System 2
50 to 500 V 200 V
RPQ
Setpoint Voltage System 2
50 to 530 V 200 V
RPQ L
CT generator System 2
10 to 7,000/{X} A 500/{X} A
RPQ L
Gen Rated curr. System 2
10 to 7,000 A 520 A
RPQ L
Gen rated power System 2
5 to 9,999 kW 180 kW
RPQ
Rated Voltage System 3
50 to 500 V 440 V
RPQ
Setpoint Voltage System 3
50 to 530 V 440 V
RPQ L
CT generator System 3
10 to 7,000/{X} A 500/{X} A
RPQ L
Gen Rated curr. System 3
10 to 7,000 A 270 A
RPQ L
Gen rated power System 3
5 to 9,999 kW 200 kW
RPQ
Rated Voltage System 4
50 to 500 V 220 V
RPQ
Setpoint Voltage System 4
50 to 530 V 220 V
RPQ L
CT generator System 4
10 to 7,000/{X} A 500/{X} A
RPQ L
Gen Rated curr. System 4
10 to 7,000 A 480 A
RPQ L
Gen rated power System 4
5 to 9,999 kW 180 kW