Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 89/174
Emergency Power; Parameters
Parameter 164
Emergency power
ON
Emergency power ON/OFF
ON ................ If the control is in AUTOMATIC or TEST mode and a mains failure
occurs, the engine is started and an automatic emergency power op-
eration is performed. The subsequent parameters of this function are
displayed. Emergency power is also initiated by the detection of a
breaker failure when the MCB is to be closed. In order to enable this,
the Parameter 158 ("Supervision MCB") must be configured to
"ON".
OFF
.............. Emergency power operation is not enabled and the subsequent para-
meters of this function are not displayed.
Parameter 165
Emergency power
start del. 00.0s
Start delay for emergency power 0.5 to 99.9 s
In order to start the engine and to carry out an emergency power operation, the
mains must fail for at least this delay time.