Manual 37278B GCP-30 Series - Genset Control
Page 30/174 © Woodward
Password Configuration
NOTE
Once a password has been set, it will not change unless a person alters that parameter with access to,
it regardless of how often the configuration mode is accessed. If an incorrect code number is entered,
the code level is set to CS0 and the control is therefore locked for external users.
The control unit automatically reverts to code level CS0 two hours after the entry of a password or if
the power supply is disconnected from the control unit. By entering the correct password, the corres-
ponding level may again be accessed.
Parameter 43
Define level 1
code 0000
Code level 1 (Customer) 0000 to 9999
This parameter is only accessible with code level 2 rights. After the password has
been set for this parameter, only the personnel who are assigned this password will
have access rights to this code level. When the CS1 (Customer) password is en-
tered, only select parameters may be accessed.
The default setting for this code level (CS) is CS1 = 0 0 0 1
Parameter 44
Define level 2
code 0000
Code level 2 (Commissioner) 0000 to 9999
This parameter is only accessible with code level 2 rights. After the password has
been set for this parameter, only the personnel who are assigned this password will
have access rights to this code level. When the CS1 (Customer) password is en-
tered, only select parameters may be accessed.
The default setting for this code level (CS) is CS2 = 0 0 0 2