EasyManua.ls Logo

Woodward GCP-30 Series - Page 13

Woodward GCP-30 Series
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 13/174
Command: close GCB
Terminals 14/15
Enabling this relay will close the GCB. If the GCB closing command is configured to continuous cur-
rent (Parameter 129), in response to a missing discrete input "Reply: GCB is open" the relay is main-
tain
ed in its closed state; this also applies if the voltages of the generator and the busbar are equal. In
the event of a class F3 alarm this relay de-energizes immedately. In the event of a class F2 alarm or
for shutdown the relay does not de-energize immediately, it will de-energize if the power is less than
3.125 % of the rated generator power. If operation of the GCB is configured as a momentary pulse,
the relay de-energizes after the pulse is output. This function must be used in conjunction with an ex-
ternal holding coil for the GCB.
Command: open GCB
Terminals 41/42
Enabling this relay will open the GCB. Following "Reply: GCB is open", the relay output is de-
energized.
[GCP-32] Command: close MCB
Terminals 16/17
Enabling this relay will close the MCB. This output is always a momentary pulse. For the MCB to
remain closed an external holding coil must be used.
[GCP-32] Command: open MCB
Terminals 39/40
By enabling this relay, the MCB will open. Following "Reply: MCB is open", the relay output is de-
energized.
Relay manager
Terminals 74 to 83, 37/38, 47/48
The "Relay Manager" manages the relays listed here (Parameter 286).
Defau
lt values:
·Relay 1 to 5 = relay number (e. g. relay 1 = alarm class 1, relay 2 = alarm class 2, etc.)
·Relay 6 = Ignition / preheating
·Relay 7 = Centralized alarm

Table of Contents

Other manuals for Woodward GCP-30 Series

Related product manuals