Parameter 92
Analog input
0-00mA
Package XP, Option T701 only
P set point value: range 0 to 20 / 4 to 20 mA
The analog input of the real power controller can be switched here between
0 to 20 mA and 4 to 20 mA depending on the set point source.
0 to 20 mA ... Minimum value of the set point at 0 mA; maximum value at 20 mA.
4 to 20 mA ... Minimum value of the set point at 4 mA; maximum value at 20 mA.
CAUTION
The interchange real power set point may also be scaled. When controlling the interchange power, it is
vital to ensure that C power is not entered simultaneously with I or E power when scaling the external
analog input.
External setpoint 0/4 mA C I E I E
External setpoint 20 mA C I E E I
Parameter 93
Ext.setpoint
0mA 0000kW
Package XP, Option T701 only
P set point value: scaling minimum value C/I/E 0 to 9,999 kW
The minimum value of the generator real power is defined here (e. g. 0 kW).
Parameter 94
Ext.setpoint
20mA 0000kW
Package XP, Option T701 only
P set point value: scaling maximum value C/I/E 0 to 9,999 kW
The maximum value of the generator real power is defined here (e. g. 100 kW).