279
bit11bit12not useful
bit13bit14 auto tune PID
mode (valid in critical
oscillation mode)
00PID control
01PI control
10P control
bit15
0regular mode
1advanced mode;
S3+3
Proportion Gain (Kp)
Range132767[%]
S3+4
Integration time (TI)
032767[unit: 100ms]
0 is taken as no
integral.
S3+5
Differential time ( TD)
032767[unit: 10ms]
0 is taken as no
differential.
S3+6
PID operation zone
032767
PID adjustment band
width value
S3+7
Control death zone
032767
PID output value
will not change in
death zone
S3+8
Sampling temperature
filter coefficient
0100[%]
Filter the input
sampling
temperature in
advanced mode, 0 is
no input filter
S3+9
Differential gain( KD)
0100[%]
Only for advanced
mode (normal mode
default value is
50%), 0 is no
differential gain
S3+10
Upper limit value of
output
032767
S3+11
Lower limit value of
output
032767
S3+12
Change of Unit
Temperature Corresponds
to Change of AD Value
full scale AD value *
0.3~1%
default value is 10
16-bit no sign, only
for step PID
S3+13
PID auto tune overshoot
0enable overshoot
1 not overshoottry to
reduce the overshoot
only for step PID
S3+14
Current target value
adjusting percentage
every time in auto tune
end transition stage
Cannot adjust
16-bit no sign, only
for step PID
S3+15
Number of times
exceeding the target value
in auto tune end transition
stage when limiting the
overshoot
only for step PID,
default value is 15
S3+16
PID type and status
Bit0~bit1
00: manual mode
01: step mode
Internal use
parameters of the
system for