XL5E
T0~T4999
HT0~HT1999
ET0~ET39
XLME
T0~T4999
HT0~HT1999
ET0~ET39
The timers accumulate the 1ms, 10ms, 100ms pulse, the output contactor activates when the
accumulation reaches the set value;
TMR instruction is for common timers. The set value can be constant (K) or data register
(D).
X0
T0
X0
Y0
2s
( )
Y0
Current
value
Set
value
TMR T0 K200 K10
HT0
X0
X2
RST HT0
X0
Set
value
Current
value
Y0
t1+t2=20st1 t2
X2
TMR_A HT0 K2000 K10
Y0
Function
If X0 is ON, HT0 accumulates the
10ms pulse based on the current
value. When the accumulation value
reaches the set value K2000, the
timer output activates.
If X0 is suddenly OFF during timer
working, the timer value will be
retentive. Then X0 is ON again, the
timer will continue working.
When X2 is ON, the timer and
output will be reset.
If X0 is ON, then T0
accumulates 10ms pulse based
on the current value; when the
accumulation value reaches the
set value K200, the timer
output activates. I.e. the output
activates 2s later. If X0 is OFF,
the timer resets, the output
resets;
Appoint the set value
Normal type
Accumulation type