41
1. Instruction format
TMR T0 K200
K10
S1 S2 S3
TMR_A T0 K2000
K10
S1 S2 S3
Reset the timer and output:
RST T0
S1
S1: timer (T0, HT10)
S2: set time (such as K100)
S3: time unit (K11ms, K1010ms, K100100ms)
Power-off not retentive, not accumulation
(1) Time unit is 1ms, set time is K100, the real time is 1ms *100=0.1s
TMR T0 K100 K1
X0
TMR T0 D0 K1
X0
X1
MOV K100 D0
Set value is constant K set value is register D
(2) Time unit is 10ms, set time is K10, the real time is 10ms*10=0.1s
TMR T0 K10 K10
X0
TMR T0 D0 K10
X0
X1
MOV K10 D0
Set value is constant K set value is register D
(3) Time unit is 100ms, set time is K1, the real time is 100ms*1=0.1s
TMR T0 K1 K100
X0
TMR T0 D0 K100
X0
X1
MOV K1 D0
Set value is constant K set value is register D
Power-off retentive, accumulation
(1) Time unit is 1ms, set time is K100, the real time is 1ms *100=0.1s
TMR_A HT0 K100
K1
X0
TMR_A HT0 D0
K1
X0
X1
MOV K100 D0
Set value is constant K set value is register D
(2) Time unit is 10ms, set time is K10, the real time is 10ms*10=0.1s
(Not accumulation)
(Accumulation)