EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - Safety Messages

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3 Parameter Table
54 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
71 Speed/Torque Control Switch
Open: Speed Control
Closed: Torque Control
179
73 Door Switch NC
Closed: The drive panel door is closed. The dO fault occurs if the door is opened while
the main power supply is turned on.
Note: 1. This setting is available from the drive software versions S0108 and later.
2. Make sure to input the door switch signal to the contact inputs.
179
75 Up 2 Command
Used to control the bias added to the frequency reference by the Up/Down 2 function.
The Up 2 and Down 2 commands must always be used in conjunction with one another.
179
76 Down 2 Command
77 ASR Gain Switch
Open: ASR proportional gain 1 (C5-01)
Closed: ASR proportional gain 2 (C5-03)
180
78
External Torque Reference
Polarity Inversion
Open: Forward torque reference
Closed: Reverse polarity
180
80
Synchronous Transfer
Command from Drive to
Commercial Power Supply
Closed: Synchronous Transfer from the drive to a commercial power supply is enabled.
Note: This function cannot be used simultaneously with settings 80 and 81. If
switching between settings 80 and 81, set the active one to be disabled before
setting the other one to be enabled.
181
81
Synchronous Transfer
Command from Commercial
Power Supply to Drive
Closed: Synchronous Transfer from a commercial power supply to the drive is enabled.
Note: This function cannot be used simultaneously with settings 80 and 81. If
switching between settings 80 and 81, set the active one to be disabled before
setting the other one to be enabled.
181
82
Close Signal for Commercial
Power Supply Side Breaker
Open: The commercial power supply side breaker is open.
Closed: The commercial power supply side breaker is closed.
Note: 1. Use this setting if the Synchronous Transfer is used.
2. Make sure the contact input terminal set to 82 closes as an answer signal when
the commercial power supply side breaker is closed and opens when the
commercial power supply side breaker is open.
181
83
Close Signal for Drive
Secondary Side Breaker
Open: The drive secondary side breaker is open.
Closed: The drive secondary side breaker is closed.
Note: 1. Use this setting if the Synchronous Transfer is used.
2. Make sure the contact input terminal set to 82 closes as an answer signal when
the commercial power supply side breaker is closed and opens when the
commercial power supply side breaker is open.
181
No.
(Addr.)
Name Description Setting Page
H2: Contact Outputs
H2-01
(40BH)
Contact Output 1
Function Selection
Refer to H2 Contact Output Settings on page 56 for a description of setting
values.
Default: 10E
<45>
Min: 0
Max: 1FF
181
H2-02
(40CH)
Contact Output 2
Function Selection
Refer to H2 Contact Output Settings on page 56 for a description of setting
values.
Default: E
Min: 0
Max: 1FF
181
H1 Contact Input Selections
H1-
Setting
Function Description
Reference
Page
CLV
V/f
OLV
common
All Modes
common
All Modes
common_
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 54 ページ 013年10月11日 金曜日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals