1.3  Parameter Table
60  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
H3 Analog Input Settings
H3- 
Setting
Function Description Page
0 Frequency Bias
10 V = E1-04 (maximum output frequency)
195
1 Frequency Gain
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of 
-100 to 0%.
195
2
Auxiliary Frequency 
Reference (Used as a 
Multi-Step Speed 2)
10 V = E1-04 (maximum output frequency)
195
3
Auxiliary Frequency 
Reference (3rd Step Analog)
10 V = E1-04 (maximum output frequency)
195
4 Output Voltage Bias
10 V = E1-05 (motor rated voltage)
195
5 Accel/Decel Time Gain
10 V = 100%
196
6 DC Injection Braking Current
10 V = Drive rated current
196
7
Overtorque/Undertorque 
Detection Level
10 V = Drive rated current (V/f)
10 V = Motor rated torque (OLV, CLV)
196
8
Stall Prevention Level During 
Run
10 V = Drive rated current
196
9
Output Frequency Lower 
Limit Level
10 V = E1-04 (maximum output frequency)
196
B PID Feedback
10 V = 100%
196
C PID Setpoint Value
10 V = 100%
197
D Frequency Bias
10 V = E1-04 (maximum output frequency)
197
F Through Mode
Set this value when using the terminal in the pass-through mode.
197
10 Forward Torque Limit
10 V = Motor rated torque
197
11 Reverse Torque Limit
10 V = Motor rated torque
197
12 Regenerative Torque Limit
10 V = Motor rated torque
197
13
Torque Reference/Torque 
Limit
10 V = Motor rated torque
197
14 Torque Compensation
10 V = Motor rated torque
197
15 General Torque Limit
10 V = Motor rated torque
197
16 Differential PID Feedback
10 V = 100%
197
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
CLV
V/f
OLV
MV1000ParameterGuide_E_conditional.book  60 ページ  2013年10月11日 金曜日 午後8時18分