EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - Terminals

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 59
62
Inrush Current Suppression
Circuit Fault
Open: The inrush current suppression circuit fault has been detected.
Note: This setting is available from the drive software versions S0109 and later.
191
100 to 160
Function 0 to 60 with Inverse
Output
Inverts the output switching of the contact output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.
Example: 108: Reverses the output of 8 (During Baseblock)
14C: Reverses the output of 4C (During Fast Stop)
191
No.
(Addr.)
Name Description Setting Page
H3: Analog Inputs
H3-01
(410H)
Analog Input 1
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
192
H3-02
(434H)
Analog Input 1
Function Selection
Sets the function of analog input 1.
Default: 0
Min: 0
Max: FF
193
H3-03
(411H)
Analog Input 1 Gain
Sets the level of the input value selected in H3-02 when 10 V is input at
analog input 1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
193
H3-04
(412H)
Analog Input 1 Bias
Sets the level of the input value selected in H3-02 when 0 V is input at
analog input 1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
193
H3-09
(417H)
Analog Input 2
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
194
H3-10
(418H)
Analog Input 2
Function Selection
Sets the function of analog input 2.
Default: 0
Min: 0
Max: 32
194
H3-11
(419H)
Analog Input 2 Gain
Sets the reference value for the function assigned for analog input 2 in %
units when 10 V is input.
Default: 100.0%
Min: -999.9%
Max: 999.9%
194
H3-12
(41AH)
Analog Input 2 Bias
Sets the amount of bias for the function assigned for analog input 2 in %
units when 0 V is input.
Default: 0.0%
Min: -999.9%
Max: 999.9%
194
H3-13
(41BH)
Analog Input Filter
Time Constant
Sets a primary delay filter time constant for analog inputs 1 and 2. Used for
noise filtering.
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
194
H3-14
(41CH)
Analog Input
Terminal Enable
Selection
Determines which analog input terminals will be enabled when the analog
input is set for “PID target value” (H3- = C).
1: Analog input 1 only
2: Analog input 2 only
3: Analog inputs 1 and 2 only
Default: 3
Min: 1
Max: 3
194
H3-16
(2
F0H)
Analog input 1
Offs
et
Adds an offset when the analog signal to analog input 1 is at 0 V.
Default: 0
Min: -500
Max: 500
195
H3-17
(2F1H)
Analog input 2
Offset
Adds an offset when the analog signal to analog input 2 is at 0 V.
Default: 0
Min: -500
Max: 500
195
H2 Contact Output Settings
H2-
Setting
Function Description Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 59 ページ 013年10月11日 金曜日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals