4.3 The Drive and Programming Modes
86 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
■ Simplified Setup Using the Setup Group
In the Setup Group, the drive lists the 32 parameters registered as User Parameters. It provides a simplified way to get the
application running right away by showing only the most important parameters. Refer to Figure 4.7 as an operation
example.
Note: For details on the parameters of the setup mode, refer to Chapter 1 Parameter List of the FSDrive-MV1000 Parameter Guide.
Key operations in the setup mode are shown in the following figure.
In this example, the Setup Group is accessed to change b1-01 from 1 to 0. This changes the source of the frequency
reference from the control circuit terminals to the digital operator.
Figure 4. 7
Figure 4.7 Setup Group Example
<1> To edit a parameter set value, go to the right steps.
To confirm the parameter list displayed in the Setup Group, go to the steps below.
<2> To go back to the initial screen, press .
To edit another parameter in the Setup Group, press or .
←
→
←
→
Control Circuit
Terminal
Parameter Display
Digital Operator
<1>
<2>
Frequency reference
appears when
powered up
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.0A
DRV
FREF (OPR)
Rdy
JOG FWD FWD/REV
LSEQ
LREF
HELP
- MODE - PRG
Quick Setting
DATA
FWD
Entry Accepted
- SETUP -
b1-01= 1
∗1∗
Analog Input
PRG
Ref Source 1
Rdy
Home FWD DATA
- SETUP -
A1-06= 0
∗0∗
General
PRG
Application Sel
Rdy
Home FWD DATA
- SETUP -
A1-02= 2
∗2∗
Open Loop Vector
PRG
Control Method
Rdy
Home FWD DATA
- SETUP -
b1-02= 1
∗1∗
Digital Inputs
PRG
Run Source 1
Rdy
Home FWD DATA
- SETUP -
L3-04= 1
∗1∗
General Purpose
PRG
StallP Decel Sel
Rdy
Home FWD DATA
“1”
- SETUP -
b1-01= 1
∗1∗
Analog Input
PRG
Ref Source 1
Rdy
FWD
“1”
- SETUP -
b1-01= 0
∗1∗
Operator
PRG
Ref Source 1
Rdy
FWD