5.6 F: Options
258 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
The following setting values are available when using the PROFINET communication option card (SI-EP3).
0: Static
2: DCP
When F7-13 = 0, set parameters F7-01 to F7-12 [IP Address 1 to Gateway Address 4] to set the IP Address. Be sure to set a different IP
address for each drive on the network.
F7-14: Duplex Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
F7-14
(03F2)
Duplex Mode Selection Sets the duplex mode setting method. 1
(0 - 8)
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
Port 1 is set to Half and port 2 is set to Auto.
4 : Half/Full
Port 1 is set to Half and port 2 is set to Full.
5 : Auto/Half
Port 1 is set to Auto and port 2 is set to Half.
6 : Auto/Full
Port 1 is set to Auto and port 2 is set to Full.
7 : Full/Half
Port 1 is set to Full and port 2 is set to Half.
8 : Full/Auto
Port 1 is set to Full and port 2 is set to Auto.
F7-15: Communication Speed Selection
No.
(Hex.)
Name Description
Default
(Range)
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed. 10
(10, 100 - 102)
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
Set this parameter when F7-14 = 0 or 2 [Duplex Mode Selection = Half/Half or Full/Full].
F7-16: Timeout Value
No.
(Hex.)
Name Description
Default
(Range)
F7-16
(03F4)
Timeout Value Sets the detection time for a communications timeout. 0.0 s
(0.0 - 30.0 s)
Note:
Set this parameter to 0.0 to disable the connection timeout function.