Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 275
Setting Value Function Reference
72 High PI2 Control Feedback Level 290
89 Output Current Lim 291
94 Loss of Prime 291
95 Thermostat Fault 291
96 High Feedback 291
97 Low Feedback 291
9E Low PI Auxiliary Control Level 291
9F High PI Auxiliary Control Level 291
A9 RELAY Operator Control 291
AB Thrust Mode 291
AC Setpoint Not Maintained 291
B2 BAS Interlock 292
B8 Pump Fault 292
B9 Transducer Loss 292
Setting Value Function Reference
BA PI Auxiliary Control Active 292
BB Differential Feedback Exceeded 292
BC Sleep Active 292
BD Start Delay 292
BE Pre-Charge 292
C0 HAND Mode 292
C1 AUTO Mode 293
C2 OFF Mode 293
C3 Main Feedback Lost 293
C4 Backup Feedback Lost 293
100 to 1C4
Inverse Outputs of 0 to C4
Sets an inverse output of the function for the MFDO.
Put a 1 at the front of the function setting to set inverse
output. For example, set 138 for inverse output of 38
[Drive Enabled].
293
*1 Inverse output is not available.
*2 You cannot set this parameter on models D169 to D273, A154 to A248, and B065 to B302.
â–  Extended MFDO1 to MFDO3 Function Selection
You can set MFDO functions to bit 0 to bit 2 [MEMOBUS MFDO1 to 3] of MEMOBUS register 15E0 (Hex.). Use
H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func] to select the function.
Figure 5.43 Functional Block Diagram of MEMOBUS Multi-function Output
Table 5.41 MEMOBUS MFDO Registers
Register number
(Hex.)
Name
15E0
bit0 MEMOBUS MFDO 1
bit1 MEMOBUS MFDO 2
bit2 MEMOBUS MFDO 3
Note:
• Refer to MFDO Setting Values on page 280 for more information about MFDO setting values.
• When you do not set functions to H2-40 to H2-42, set them to F.
â–  Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, and H2-66 [Term M1-M2 Secondary Function to Term M5-M6 Secondary Function] to set the
function of the output signal for which logical operations are performed.
Use H2-61, H2-64, H2-67 [Term M1-M2 Logical Operation to Term M5-M6 Logical Operation] to set the logical
operation.

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control