Parameter Details
5
5.10 o: Keypad-Related Settings
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 373
■ o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2 Sets the data log monitor. This parameter is only available on an HOA keypad. 102
(000, 101 - 1299)
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
■ o5-05: Log Monitor Data 3
No.
(Hex.)
Name Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3 Sets the data log monitor. This parameter is only available on an HOA keypad. 103
(000, 101 - 1299)
Note:
Set the U monitor number you want to log.
For example, to show U1-03 [Output Current], set o5-05 = 103. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-06: Log Monitor Data 4
No.
(Hex.)
Name Description
Default
(Range)
o5-06
(1556)
RUN
Log Monitor Data 4 Sets the data log monitor. This parameter is only available on an HOA keypad. 107
(000, 101 - 1299)
Note:
Set the U monitor number you want to log.
For example, to show U1-07 [DC Bus Voltage], set o5-06 = 107. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-07: Log Monitor Data 5
No.
(Hex.)
Name Description
Default
(Range)
o5-07
(1557)
RUN
Log Monitor Data 5 Sets the data log monitor. This parameter is only available on an HOA keypad. 108
(000, 101 - 1299)
Note:
Set the U monitor number you want to log.
For example, to show U1-08 [Output Power], set o5-07 = 108. When it is not necessary to set a data log monitor, set this parameter to 000.
■ o5-08: Log Monitor Data 6
No.
(Hex.)
Name Description
Default
(Setting Range)
o5-08
(1558)
RUN
Log Monitor Data 6 Sets the data log monitor. This parameter is only available on an HOA keypad. 0
(0, 101 - 1299)
Note:
• Set the U monitor number you want to log.
For example, to display U1-01 [Frequency Reference], set o5-08 = 101. When it is not necessary to set a data log monitor, set this
parameter to 0.