9.5 b: Application
602 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-34
(019F)
RUN
PID Output Lower Limit
Level
Sets the output lower limit for the PID control as a percentage of the Maximum Output
Frequency.
0.0%
(-100.0 - +100.0%)
218
b5-35
(01A0)
RUN
PID Input Limit Level Sets the output upper limit for the PID control as a percentage of the Maximum Output
Frequency.
1000.0%
(0.0 - 1000.0%)
218
b5-38
(01FE)
PID User Unit Display
Scaling
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
100.00
(0.01 - 600.00)
218
b5-39
(01FF)
PID User Unit Display
Digits
Sets the number of digits to set and show the PID setpoint.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
2
(0 - 3)
218
b5-41
(0160)
PID Output 2 Unit Sets the display units in U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4
Digits].
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
0
(0 - 50)
218
b5-42
(0161)
RUN
PID Output 2 Calc Mode Sets how to calculate the original PID output.
0 : Linear
1 : Square Root
2 : Quadratic
3 : Cubic
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
0
(0 - 3)
219
b5-43
(0162)
RUN
PID Out2 Monitor MAX
Upper4 Dig
Sets the upper 4 digits of the maximum monitor value. Used with b5-44 [PID Out2
Monitor MAX Lower4 Dig] to set maximum monitor value of U5-14 [PID Out2 Upr4
Digits] and U5-15 [PID Out2 Lwr4 Digits] at maximum frequency.
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
0
(0 - 9999)
219
b5-44
(0163)
RUN
PID Out2 Monitor MAX
Lower4 Dig
Sets the lower 4 digits of the maximum monitor value. Used with b5-43 [PID Out2
Monitor MAX Upper4 Dig] to set maximum monitor value of U5-14 [PID Out2 Upr4
Digits] and U5-15 [PID Out2 Lwr4 Digits] at maximum frequency.
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
0.00
(0.00 - 99.99)
220
b5-45
(0164)
RUN
PID Out2 Monitor MIN
for Linear
Sets the minimum display value to show when at zero speed. Only effective when b5-42 =
0 [PID Output 2 Calc Mode = Linear].
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
0.0
(0.0 - 999.9)
220