9.19 Defaults by Bypass and Drive Model
690 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No. Name Unit Default
- Drive Model -
D114
A104
D143
A130
D169
A154
D211
A192
D273
A248
o2-04
Drive Model (KVA)
Selection
Hex. 70 72 73 74 75
E2-11
Motor Rated
Power
HP
(kW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
E2-02 Motor Rated Slip Hz 1.80 1.33 1.60 1.43 1.39
E2-03
Motor No-Load
Current
A 21.9 38.2 44.0 45.6 72.0
E2-05
Motor Line-to-Line
Resistance
Ω 0.064 0.039 0.030 0.022 0.023
E2-06
Motor Leakage
Inductance
% 20.8 18.8 20.2 20.5 20.0
E2-10 Motor Iron Loss W 699 823 852 960 1200
L2-02
Power Loss Ride
Through Time
s 2.0 2.0 2.0 2.0 2.0
L2-03
Minimum Baseblock
Time
s 1.1 1.1 1.2 1.3 1.5
L2-04
Powerloss V/f
Recovery Ramp
Time
s 0.6 0.6 1 1 1
L2-05
Undervoltage
Detection Lvl (Uv1)
- 190 190 190 190 190
L3-24
Motor Accel Time
for Inertia Cal
s 0.323 0.32 0.387 0.317 0.533
L8-02
Overheat Alarm
Level
°C 115 110 110 110 110
L8-09
Output Ground Fault
Detection
- 1 1 1 1 1
L8-35
Installation Method
Selection
- 2 2 2 0 0
L8-38
Carrier Frequency
Reduction
- 2 2 2 2 2
n1-01
Hunting Prevention
Selection
- 1 1 1 1 1
n1-03
Hunting Prevention
Time Constant
ms 10 10 10 10 10
◆ 480 V
No. Name Unit Default
-
Bypass
Model
-
B001
B002
B003
B004
B007 B011 B014 B021 B027 B034 B040
o2-04
Drive Model
(KVA)
Selection
Hex. 95 97 99 9A 9B 9D 9E 9F
E2-11
Motor Rated
Power
HP
(kW)
2
(1.5)
4
(3.0)
5
(4.0)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50