Parameter List
9
9.19 Defaults by Bypass and Drive Model
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 691
No. Name Unit Default
-
Bypass
Model
-
B001
B002
B003
B004
B007 B011 B014 B021 B027 B034 B040
o2-04
Drive Model
(KVA)
Selection
Hex. 95 97 99 9A 9B 9D 9E 9F
E2-11
Motor Rated
Power
HP
(kW)
2
(1.5)
4
(3.0)
5
(4.0)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
b3-11
Spd Est
Method
Switch-over
Level
% 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
b3-12
Speed Search
Current
Deadband
- 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-04
Energy Saving
Coefficient
Value
- 338.8 265.7 245.8 189.5 145.38 140.88 126.26 115.74
C6-02
Carrier
Frequency
Selection
- 2 2 2 2 2 2 2 2
E2-01
Motor Rated
Current (FLA)
A 4.80 7.60 11.00 14.00 21.0 27.0 34.0 40.0
E2-02
Motor Rated
Slip
Hz 2.50 2.70 2.70 1.50 1.30 1.70 1.60 1.67
E2-03
Motor No-
Load Current
A 1.4 1.9 2.3 2.6 4 5.6 7.6 7.8
E2-05
Motor Line-to-
Line
Resistance
Ω 10.1 4.360 3.333 1.595 1.152 0.922 0.550 0.403
E2-06
Motor
Leakage
Inductance
% 18.3 19 19.3 18.2 15.5 19.6 17.2 20.1
E2-10
Motor Iron
Loss
W 53 105 130 193 263 385 440 508
L2-02
Power Loss
Ride Through
Time
s 0.7 0.9 1.3 1.3 1.7 2.0 2.0 2.0
L2-03
Minimum
Baseblock
Time
s 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.0
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.6 0.6
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time for
Inertia Cal
s 0.166 0.145 0.154 0.168 0.175 0.265 0.244 0.317
L8-02
Overheat
Alarm Level
°C 115 115 95 95 127 127 127 123
L8-09
Output Ground
Fault
Detection
- 0 0 0 0 0 0 0 1
L8-35
Installation
Method
Selection
- 2 2 2 2 2 2 2 2
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2