EasyManuals Logo

YASKAWA HV600 User Manual

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
3.3 Main Circuit Wiring
86 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Model
H6BP
Motor Wiring
Standard Motor
Terminal Block TB1
Ground Wiring
Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
Panel
Terminal Block
TB4
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
A068
14-2 32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A080 14-8 or 6-2/
0
50 or 120
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A104 14-8 or 6-2/
0
50 or 120
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A130 (1-2) x (6)
or (4) or (3-
4/0)
(1-2) x 80
or 100 or
150
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A154 6 - 350
kcmil
275
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A192
6-350 kcmil 275 14 - 2/0 120 24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
A248 (1-2) x (4-
500 kcmil)
(1-2) x 500 14 - 2/0 120 24-16 4.4 to 5.3 24-18
*1
8.85 to
10.62
26-14 4 26-10 5.3 to 7.1
*1 24-16 is acceptable for solid wire or ferrule use only.
â–  480 V Enclosed Wire Gauges and Torques
Table 3.9 Input Wiring
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
B001 20 14-8 20 15 (14-10) or (8-3/0) 50 or 120
B002
20 14-8 20 15 (14-10) or (8-3/0) 50 or 120
B003
20 14-8 20 15 (14-10) or (8-3/0) 50 or 120
B004
20 14-8 20 15 (14-10) or (8-3/0) 50 or 120
B007 20 14-8 20 20 (14-10) or (8-3/0) 50 or 120
B011
20 14-8 20 25 (14-10) or (8-3/0) 50 or 120
B014
20 14-8 20 35 (14-10) or (8-3/0) 50 or 120
B021
45 10, 8 or (6-2) 35, 40, or 50 50 (14-10) or (8-3/0) 50 or 120
B027
45 10, 8 or (6-2) 35, 40, or 50 60 (14-10) or (8-3/0) 50 or 120
B034
63 10, 8 or (6-2) 35, 40, or 50 70 (14-10) or (8-3/0) 50 or 120
B040
63 10, 8 or (6-2) 35, 40, or 50 80 (14-10) or (8-3/0) 50 or 120
B052
100 8-2/0 200 110 (14-10) or (8-3/0) 50 or 120
B065
100 8-2/0 200 115 (14-10) or (8-3/0) 50 or 120
B077
150 8-3/0 120 150 (14-10) or (8-3/0) 50 or 120
B096
150 14-10 or 8-3/0 50 or 120 150 (14-10) or (8-3/0) 50 or 120
B124
175 4 - 4/0 225 250 4-4/0 225
B156
250 3/0-350 kcmil 225 250 3/0-350 kcmil 225
B180
250 3/0-350 kcmil 225 250 3/0-350 kcmil 225
B240
400 (1-2) x (2/0-500 kcmil) (1-2) x 442 500 (1-2) x (2/0-500 kcmil) (1-2) x 442
B302
600 (1-2) x (2/0-500 kcmil) (1-2) x 442 600 (1-2) x (2/0-500 kcmil) (1-2) x 442

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control