55
3.3 Wiring the iC9200
3. Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
4. The shield bus must always be earthed. Keep all cable connections as short as possi-
ble. To earth the shield bus, connect a PE conductor to the shield bus via a shield clamp
and screw it to the base plate as close as possible and with low impedance.
Base plate
PE conductor screwed to base plate
(3)
Wiring 16x Periphery Modules
(a) Terminal Block Connectors
• The 16x periphery module has a removable terminal block for wiring.
• With the wiring of the terminal block a "push-in" spring-clip technique is used. This allows a quick and easy
connection of your signal and supply lines.
• The clamping off takes place by means of a screwdriver.
• Please use copper wire only!
Clic
1
2
CAUTION
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description, hazardous voltages
are not allowed to be connected to the corresponding terminal block!
Danger of injury from electrical shock and damage to the CPU respectively to the modules!
Put the iC9200 Series in a safe, powered down state before starting installation, disassembly
or wiring of the iC9200 Series modules!
1
2
3
Installation and Wiring