1.5 E: Motor Parameters
120 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 0: V/f Control
Setting 1: Open Loop Vector Control
E3-04 to E3-13
Parameters E3-04 through E3-14 set up the V/f pattern used for motor 2 like shown in
Figure 1.42.
Figure 1.42
Figure 1.42 V/f Pattern for Motor 2
Note: 1. The following condition must be true when setting up the V/f pattern: E3-09 =< E3-07 =< E3-06 <= E3-
11 <= E3-04
2. To make the V/f pattern a straight line set E3-09 = E3-07. In this case the E3-08 setting is disregarded.
No. Parameter Name Setting Range Default
E3-01 Motor 2 Control Mode Selection 0 or 2 0
No.
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class unit.
<2> Default setting is determined by the control mode for motor 2.
Parameter Name Setting Range Default
E3-04 Motor 2 Max Output Frequency 40.0 to 400.0 Hz 50.0 Hz
E3-05 Motor 2 Max Voltage 0.0 to 255.0 <1> 200.0 V <1>
E3-06 Motor 2 Base Frequency 0.0 to 400.0 50.0 Hz
E3-07 Motor 2 Mid Output Frequency 0.0 to 400.0 <2>
E3-08 Motor 2 Mid Output Frequency Voltage 0.0 to 255.0 <1> <2>
E3-09 Motor 2 Minimum Output Frequency 0.0 to 400.0 <2>
E3-10 Motor 2 Minimum Output Frequency Voltage 0.0 to 255.0 <1> <2>
E3-11 Motor 2 Mid Output Frequency 2 0.0 to 400.0 0.0 Hz
E3-12 Motor 2 Mid Output Frequency Voltage 2 0.0 to 255.0 <1> 0.0 Vac
E3-13 Motor 2 Base Voltage 0.0 to 255.0 <1> 0.0 Vac
Output (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07
E3-06
E3-11
E3-04