1.7 H: Terminal Functions
140 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 0: 3-Wire Sequence
When one of the digital inputs is programmed for 3-wire control, that input becomes a
forward/reverse directional input, S1 becomes the Run command input, and S2 becomes the
Stop command input.
The drive will start the motor when the Run input S1 is closed for longer than 50ms. The
drive will stop the operation when the Stop input S2 is released for a brief moment.
Whenever the input programmed for 3-wire sequence is open, the drive will be set for
forward direction. If the input is closed, the drive is set for reverse direction.
Note: When 3-wire sequence is selected the Run and Stop command must be input at S1 and S2.
Figure 1.44
Figure 1.44 3-Wire Sequence Wiring Diagram
10 Up Command
144
65 KEB Ride-Thru 1 (N.C.)
153
11 Down Command 66 KEB Ride-Thru 1 (N.O.)
12 Forward Jog
146
67 Communications Test Mode 153
13 Reverse Jog 68 High-Slip Braking 153
14 Fault Reset
147
6A Drive Enable 154
15 Fast-Stop (N.O.)
147
75 Up 2 Command
154
16 Motor 2 Selection
148
76 Down 2 Command
17 Fast-stop (N.C.)
147
7A KEB Ride-Thru 2 (N.C.)
156
18 Timer Function Input
148
7B KEB Ride-Thru 2 (N.O.)
19 PID Disable
148
7C Short-Circuit Braking (N.O.)
156
1A Accel/Decel Time Selection 2
149
7D Short-Circuit Braking (N.C.)
1B Program Lockout
149
7E
Forward/Reverse Detection (V/f
Control with Simple PG Feedback)
156
1E Reference Sample Hold
149
7F Bi-directional PID output enable 156
20 to 2F External Fault
150
90 to 96 FBD’s Digital Input 1 to 7 157
30 PID Integral Reset
151
9F FBD’s Disable 157
Setting Function Page Setting Function Page
S1
S2
S5
SC
Run command (runs when closed)
Drive
Stop switch
(N.C.)
Run switch
(N.O.)
Stop command (stops when open)
FWD/REV (Multi-function input)
(H1-05 = 0)
Sequence Input Common

Table of Contents