EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.7 H: Terminal Functions
148 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 16: Motor 2 Selection
The drive has the capability to control two motors independently. A second motor may be
selected using a multi-function digital input (H1- = 16) as shown in Figure 1.50.
Figure 1.50
Figure 1.50 Motor Selection
Motor 2 is selected when the input set for Motor 2 Selection closes. When operating motor
2,
•E3- and E4- become valid for motor control. Refer to E3: V/f Characteristics for
Motor 2 on page 119 and E4: Motor 2 Parameters on page 121 for details.
accel/decel times set in parameters C1-05/06/07/08 are activated (Refer to C1-01 to C1-
08: Accel/Decel Times 1 to 4 on page 77 for details).
E4-14 is used as gain for slip compensation instead of C3-01.
E4-15 is used as gain for torque compensation instead of C4-01.
a digital output programmed for “Motor 2 Selection” (H2-01/02/03 = 1C) will be
switched on.
Note: 1. When using 2 motors, the motor overload operation selection (OL1) set to L1-01 applies to both motor
1 and motor 2.
2. It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger a "rUn"
alarm.
Setting 18: Timer Function Input
This setting configures a digital input terminal as the input for the timer function. Refer to
b4: Delay Timers on page 58 for details.
Setting 19: PID Control Cancel
When the PID Function has been enabled by b5-01 (PID Mode Selection), it can be
indefinitely disabled by closing a digital input configured as a PID Disable (H1- = 19).
When the input is released, the drive resumes PID operation. The PID Block Diagram on
page 63 illustrates how the function works.
M
M
Drive
Motor 1
Motor 2
Motor switch input

Table of Contents

Related product manuals