EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.7 H: Terminal Functions
166 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on
page 207 for details on setting the detection width.
Setting 14: User Set Speed Agree 2 (fref / fset Agree 2)
Closes whenever the actual output frequency and the frequency reference are within the
Speed Agree Width (L4-04) of the programmed Speed Agree Level (L4-03). As the
detection level L4-03 is a signed value, detection works in the specified direction only.
Figure 1.60
Figure 1.60 User Set Speed Agree 2 Example with Positive L3-04 Value
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on
page 207 for details on setting the detection width.
Setting 15: Frequency Detection 3
Output is closed as long as the output frequency is below the detection level set in L4-03
plus the hysteresis set in L4-04. It closes when the output frequency falls below L4-03. As
the detection level L4-03 is a signed value, the detection works in the specified direction
only.
Status Description
Open Output frequency or frequency reference are outside the range of L4-03 ± L4-04
Closed Output frequency and the frequency reference are both with in the range of L4-03 ± L4-04
Status Description
Open Output frequency exceeded L4-03 plus L4-04
Closed Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
Output
frequency
+/- L4-02
User Set
Speed Agree 2
OFF
ON
Frequency
reference
Frequency
reference
Output
frequency
L4-01

Table of Contents

Related product manuals