1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 167
Parameter Details
1
Figure 1.61
Figure 1.61 Frequency Detection 3 Example with Positive L3-04 Value
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on
page 207 for details on setting the detection width.
Setting 16: Frequency Detection 4
Output closes whenever the output frequency is equal to or above the detection level set in
L4-03. The output opens when the output frequency falls below L4-03 minus the hysteresis
set in L4-04. As the detection level L4-03 is a signed value, the detection works in the
specified direction only.
Figure 1.62
Figure 1.62 Frequency Detection 4 Example with Positive L3-04 Value
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on
page 207 for details on setting the detection width.
Status Description
Open Output frequency is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
Closed Output frequency exceeded L4-03
Output
frequency
L4-04
Frequency
detection 3
ON
OFF
L4-03
Output
frequency
L4-04
Frequency
Detection 4
ON
OFF
L4-03