1.1 A: Initialization
24 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table 1.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
2.
Press to display the value set to A1-02.
⇒
3.
Press and , making sure that the setting values
cannot be changed.
4.
Press to return to the first display.
⇒
Step Display/Result
1.
Press to enter the parameter setup display.
⇒
2.
Press to select the flashing digits as shown.
⇒
“01 flashes
3.
Press to scroll to A1-04.
⇒
4. Enter the password “1234”. ⇒
5.
Press to save the new password.
⇒
6. Drive returns to the parameter display. ⇒
7.
Press and scroll to A1-02.
⇒
8.
Press to display the value set to A1-02.
⇒
“0” flashes
9.
Use and to set the desired value.
⇒
Open Loop Vector Control
Step Display/Result