1.1 A: Initialization
28 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 4: HVAC Fan Application
Table 1.11 HVAC Fan: Parameter Settings
Table 1.12 HVAC Fan: Preferred Parameters (A2-01 to A2-16)
Setting 5: Compressor Application
Table 1.13 Compressor: Parameter Settings
E1-03 V/f Pattern Selection −−
No. Parameter Name Optimum Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C6-01 Duty Rating 1: Normal Duty
C6-02 Carrier Frequency Selection 3: 8.0 kHz
H2-03 Terminals P2 Function Selection 39: Watt Hour Pulse Output
L2-01
Momentary Power Loss Operation
Selection
2: CPU Power Active - Drive will restart if
power returns prior to control power supply
shut down.
L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
L8-38 Carrier Frequency Reduction 2: Enabled across entire frequency range.
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection E1-03 V/f Pattern Selection
b1-02 Run Command Selection E1-04 Max Output Frequency
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
C1-01 Acceleration Time 1 H3-11 Terminal A2 Gain Setting
C1-02 Deceleration Time 1 H3-12 Terminal A2 Input Bias
C6-02 Carrier Frequency Selection L2-01
Momentary Power Loss Operation
Selection
d2-01 Frequency Reference Upper Limit L8-03
Overheat Pre-Alarm Operation
Selection
d2-02 Frequency Reference Lower Limit o4-12 kWH Monitor Initial Value Selection
No. Parameter Name Optimum Setting
A1-02 Control Method Selection 0: V/f Control
No. Parameter Name No. Parameter Name