1.1 A: Initialization
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 29
Parameter Details
1
Table 1.14 Compressor: Preferred Parameters (A2-01 to A2-16):
Setting 6: Hoist Application
Note: 1. Read the instructions listed in Notes on Controlling the Brake when Using the Hoist Application
Preset on page 30 when using Hoist Application Preset
2. Perform Auto-Tuning after selecting the Hoist Application Preset.
Table 1.15 Hoist: Parameters and Settings
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C1-01 Acceleration Time 1 5.0 s
C1-02 Deceleration Time 1 5.0 s
C6-01 Duty Rating 0: Heavy Duty
E1-03 V/f Pattern Selection 0FH
L2-01
Momentary Power Loss Operation
Selection
1: Enabled
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection E1-03 V/f Pattern Selection
b1-02 Run Command Selection E1-07 Mid Output Frequency
b1-04 Reverse Operation Selection E1-08 Mid Output Frequency Voltage
C1-01 Acceleration Time 1 E2-01 Motor Rated Current
C1-02 Deceleration Time 1 −−
No. Parameter Name Optimum Setting
A1-02 Control Method Selection 2: Open Loop Vector Control
b1-01 Frequency Reference Selection 0: Operator
b6-01 Dwell Reference at Start 3.0 Hz
b6-02 Dwell Time at Start 0.3 s
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Duty Rating 0: Heavy Duty
C6-02 Carrier Frequency Selection 2: 5 kHz
d1-01 Frequency Reference 1 6.0 Hz
No. Parameter Name Optimum Setting