A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 299
Parameter List
A
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency Reference
Selection 1
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17.
1: Terminals - Analog input terminal A1 or A2.
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4 1 S S S 180 35
b1-02
Run Command
Selection 1
Selects the run command input source.
0: Operator - RUN and STOP keys on the
digital operator.
1: Digital input terminals
2: Memobus communications
3: Option PCB.
0 to 3 1 S S S 181 39
b1-03
Stopping Method
Selection
Selects the stopping method when the run
command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer (A new run command is
ignored if received before the timer expires)
9: Simple Positioning
0 to 3, 9 0 S S S 182 40
DC Injection Braking at Stop
cannot be selected when using
Open Loop Vector for PM motors.
b1-04
Reverse Operation
Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0,1 0 A A A 183 44
b1-07
LOCAL/REMOTE
Run Selection
Determines the operation when the Run
command source is switched from LOCAL to
REMOTE or between Run source 1 and 2 while
an external Run command is active at the new
source.
0: External Run command has to be cycled at
the new source to be activated.
1: External Run command at new source is
accepted immediately.
0,1 0 A A A 186 45
b1-08
Run Command
Selection while in
Programming Mode
0: Run command accepted only in the operation
menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during
Run
0 to 2 0 A A A 187 45