A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 319
Parameter List
A
E3-04
Motor 2 Max
Output
Frequency
These parameters set the V/f pattern for motor
2.
To set linear V/f characteristics, set the same
values for E3-07 and E3-09. In this case, the
setting for E3-08 will be disregarded. Ensure
that the four frequencies are set according to
these rules or OPE10 fault will occur:
E3-04 ≥ E3-06 > E3-07 > E3-09
40.0 to
400.0
50 Hz A A − 31A 120
E3-05
<24>
Motor 2 Max
Vo l t a g e
0.0 to
255.0
200.0
V
AA− 31B 120
E3-06
Motor 2 Base
Frequency
0.0 to E3-
04
50 Hz A A − 31C 120
E3-07
Motor 2 Mid
Output Freq.
0.0 to E3-
04
2.5 Hz
<53>
AA− 31D 120
E3-08
<24>
Motor 2 Mid
Output Freq.
Vo l t a g e
0.0 to
255.0
16.0 V
<12>
<53>
AA− 31E 120
E3-09
Motor 2 Min.
Output Freq.
0.0 to E3-
04
1.3 Hz
<53>
AA− 31F 120
E3-10
<24>
Motor 2 Min.
Output Freq.
Vo l t a g e
0.0 to
255.0
12.0 V
<12>
<53>
AA− 320 120
E3-11
<26>
Motor 2 Mid
Output
Frequency 2
0.0 to E3-
04
0.0 Hz A A − 345 120
E3-12
<24>
<52>
Motor 2 Mid
Output
Frequency
Voltage 2
0.0 to
255.0
<24>
0.0 Vac A A − 346 120
E3-13
<24>
Motor 2 Base
Vo l t a g e
0.0 to
255.0
<24>
0.0 Vac A S − 347 120
E4: Motor 2 Parameters
Use E4 parameters to control a second motor operating on the same drive.
E4-01
Motor 2 Rated
Current
Sets the motor 2 nameplate full load current in
amperes (A). This value is automatically set
during Auto-Tuning.
10 to
200% of
drive
rated
current
<57> AA− 321 121
E4-02
Motor 2 Rated
Slip
Sets the motor 2 rated slip in Hz.
Automatically set during Auto-Tuning.
0.00 to
20.00
<57> AA− 322 121
E4-03
Motor 2 Rated
No-Load
Current
Sets the magnetizing current of motor 2 in
Ampere. Automatically set during Rotational
Auto-Tuning.
0 to less
than
E4-01
<27>
<57> AA− 323 121
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
PM
ACrms Out (V)
Frequency (Hz)
E3-09 E3-07 E3-06 E3-11 E3-04
E3-05
E3-12
E3-13
E3-08
E3-10