A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 363
Parameter List
A
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
T1-00
Motor Selection
1/2
Selects which set of motor parameters are used and
set during Auto-Tuning. If Motor 2 selection
(H1- = 16) is not selected, this parameter will
not be displayed.
1: 1st Motor - E1 to E2
2: 2nd Motor - E3 to E4 (this selection is not
displayed if motor 2 has not been selected)
1, 2 1 A A − 700 251
T1-01
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<54> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control,
and 2 for Motor 2 control.
Auto-Tuning
Mode Selection
Selects the Auto-Tuning mode.
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line
Resistance
3: Rotational Auto-Tuning for V/f Control
(necessary for Energy Savings and Speed
Estimation type Speed Search)
0, 2, 3
<54>
2 or 3
in V/f
0 or 2
in OLV
2 for
Motor 2
AA− 701 252
T1-02
Motor Rated
Power
Sets the motor rated power in kilowatts (kW).
Note: If motor power is given in horsepower, power
in kW can be calculated using the following
formula: kW = HP x 0.746.
0.00 to
650.00
<12> AA− 702 252
T1-03
<24>
Motor Rated
Vo l t a g e
Sets the motor rated voltage in volts (V).
0.0 to
255.5
200.0 V A A − 703 252
T1-04
Motor Rated
Current
Sets the motor rated current in amperes (A).
10 to
200% of
drive
rated
current
<12> AA− 704 253
T1-05
Motor Base
Frequency
Sets the base frequency of the motor in Hertz (Hz).
0.0 to
400.0
60.0 Hz A A − 705 253
T1-06
Number of
Motor Poles
Sets the number of motor poles. 2 to 48 4 A A − 706 253
T1-07
Motor Base
Speed
Sets the base speed of the motor in revolutions per
minute r/min (RPM).
0 to
24000
1750
r/min
AA− 707 253
T1-11 Motor Iron Loss
Provides the iron loss for determining the Energy
Saving coefficient.
The value set to E2-10 (motor iron loss) when the
power is cycled. If T1-02 is changed, an initial
value valid for the selected capacity will be shown.
0 to
65535
14W A −− 70B 254
These values differ
depending on the motor code
value and motor parameter
settings.