A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 371
Parameter List
A
U4-16
Motor Overload
Estimate (OL1)
100% = OL1 detection level
100% = OL1
detection
level
0.1% A A A 7D8
U4-18
Frequency Reference
Source Selection
Displays the source for the frequency
reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Operator (d1-01)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus comm.
4-01 = Option
5-01 = Pulse Input
6-01 = CASE
7-01 = FBD’s
AAA 7DA
U4-19
Frequency Reference
from MEMOBUS/
Modbus Comm.
Displays the frequency reference provided by
MEMOBUS/Modbus (decimal).
AAA 7DB
U4-20
Option Frequency
Reference
Displays the frequency reference input by an
option card (decimal).
AAA 7DD
No. Name Description
Analog
Output Level
Unit
Control
Mode
Addr.
Hex
V/f
O
LV
P
M