A.2 Parameter Table
372 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
U4-21
Run Command Source
Selection
Displays the source for the Run command as
XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Operator
1 = External terminals
2 = Not used
3 = MEMOBUS/Modbus communications
4 = Option
5 = Not used
6 = CASE
7 = FBD’s
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped
in the PRG mode.
02: Run command was left on when switching
from LOCAL to REMOTE operation.
03: Waiting for the soft charge bypass
contactor after the power is switched on (UV
or UV1 flashes after 10 seconds).
04: Waiting for “Run Command Prohibited”
time period to end.
05: Fast-stop (digital input (H1- = 15),
operator)
06: b1-17 (run command given at power-up).
07: During Baseblock while coast to stop with
timer
08: Frequency reference is below minimal
reference during Baseblock
09: Waiting for Enter command
AAA 7DD
U4-22
MEMOBUS/Modbus
Communications
Reference
Displays the drive control data set by
MEMOBUS/Modbus communications
register No. 0001H as a 4 digit hexadecimal
number.
AAA 7DE
U4-23
Option Card
Reference
Displays drive control data set by an option
card as a 4 digit hexadecimal number.
AAA 7DF