EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.2 b: Application
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 61
Parameter Details
1
PID Setpoint Input Methods
When the PID control parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 (or
b1-15) becomes the PID setpoint. If b5-01 is set to 3 or 4, then the PID setpoint can be input
from one of the sources in the following table.
Table 1.21 PID Setpoint Sources
Note: A duplicate allocation of the PID setpoint input will result in an OPE alarm.
PID Feedback Input Methods
Either one feedback signal can be input for normal PID control or two feedback signals can
be input for controlling a differential process value.
Normal PID Feedback
The PID feedback can be input from one of the sources listed below.
Table 1.22 PID Feedback Sources
Application Description Sensors Used
Speed Control
Machinery speed is fed back and adjusted to meet the target value.
Synchronous control is performed using speed data from other
machinery as the target value
Tachometer
Pressure Maintains constant pressure using pressure feedback. Pressure sensor
Fluid Control Keeps flow at a constant level by feeding back flow data. Flow rate sensor
Temperature
Control
Maintains a constant temperature by controlling a fan with a
thermostat.
Thermocoupler,
Thermistor
PID Setpoint Source Settings
Analog Input A1 Set H3-02 = C
Analog Input A2 Set H3-10 = C
MEMOBUS/Modbus
Register 0006H
Set Bit 1 in register 000FH to 1 and input the setpoint to register
0006H
Pulse Input RP Set H6-01 = 2
Parameter b5-19 Set parameter B5-18 = 1 and input the PID setpoint to b5-19
PID Feedback Source Settings
Analog Input A1 Set H3-02 = B
Analog Input A2 Set H3-10 = B
Pulse Input RP Set H6-01 = 1

Table of Contents

Related product manuals