EasyManua.ls Logo

YASKAWA OYMC V1000

YASKAWA OYMC V1000
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3 C: Tuning
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual 93
Parameter Details
1
Table 1.28 Drives with Heavy Duty Default Carrier Frequency of 8 kHz
200 V Single Phase Units 200 V Three Phase Units 400 V Three Phase Units
Model
VZA~
Rated Current [A]
Model
VZA~
Rated Current [A]
Model
VZA~
Rated Current [A]
2 kHz 8 kHz 15 kHz 2 kHz 8 kHz 15 kHz 2 kHz 8 kHz 15 kHz
B1P5 9.6 8.0 6.4 21P5 9.6 8.0 6.4 40P2 1.2 1.2 0.7
B2P2 12.0 11.0 8.8 22P2 12.0 11.0 8.8 40P4 2.1 1.8 1.1
B4P0 17.5 17.5 14.0 24P0 19.6 17.5 14.0 40P7 4.1 3.4 2.0
25P5 30.0 25.0 20.0 41P5 5.4 4.8 2.9
27P5 40.0 33.0 26.4 42P2 6.9 5.5 3.3
2011 56.0 47.0 37.6 43P0 8.8 7.2 4.3
2015 69.0 60.0 48.0 44P0 11.1 9.2 5.5
45P5 17.5 14.8 8.9
47P5 23.0 18.0 10.8
4011 31.0 24.0 14.4
4015 38.0 31.0 18.6

Table of Contents

Related product manuals