Surrounding temperature is too
high.
Check the temperature surrounding the drive. Verify temperature is within
drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Load is too heavy.
Measure the output current.
Decrease the load.
Lower the carrier frequency (C6-02).
Internal cooling fan is stopped.
Replace the cooling fan. .
After replacing the drive, reset the cooling fan maintenance parameter (o4-03
= “0”).
oH1
Overheat 1 (Heatsink Overheat)
The temperature of the heatsink has exceeded 10 °C plus the default value of
L8-02.
Cause Possible Solution
Surrounding temperature is too
high.
Check the temperature surrounding the drive.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Load is too heavy.
Measure the output current.
Lower the carrier frequency (C6-02).
Reduce the load.
The internal cooling fan has
reached its performance life or has
malfunctioned.
Check the maintenance time for the cooling fan (U4-04).
If U4-04 exceeds 90%, replace the cooling fan. .
After replacing fan, reset the fan maintenance time (o4-03 = “0”).
Current flowing to control circuit
terminal +V exceeded the tolerance
level.
Check the current level of the terminal.
Set the current to the control circuit terminal to be 20 mA or less.
oH3
Motor Overheat Alarm (PTC Input)
The motor overheat signal to analog input terminal A1 or A2 exceeded the
alarm detection level.
Detection requires multi-function analog input H3-02 or H3-10 be set to “E”.
oH4
Motor Overheat Fault (PTC Input)
The motor overheat signal to analog input terminal A1 or A2 exceeded the
fault detection level.
Detection requires that multi-function analog input H3-02 or H3-10 = “E”.
Cause Possible Solution
5.2 Fault Detection
138
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide