The contactor on the inrush
prevention circuit is damaged.
Cycle power to the drive. Check if the fault reoccurs.
Replace the drive if the fault continues to occur.
Check monitor U4-06 for the performance life of the inrush prevention circuit.
Replace the drive if U4-06 exceeds 90%.
5.2 Fault Detection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
145