Motor output and motor-rated
current settings (T1-02 and
T1-04) do not match.
Check the drive and motor capacities.
Correct the settings of parameters T1-02 and T1-04.
Motor output and no-load current
settings (T1-04 and E2-03) do
not match. Data required when
Auto-Tuning for OLV Control or
Stationary Auto-Tuning.
Check the motor-rated current and no-load current.
Correct the settings of parameters T1-04 and E2-03.
Base frequency and base motor
rotations (T1-05 and T1-07) do
not match.
Set T1-05 and T1-07 to the correct value.
Er-02 Minor Fault
Cause Possible Solutions
Incorrect motor data entered
during Auto-Tuning.
Motor data entered to the T1 parameters does not match the information written
on the motor nameplate. Enter the correct data.
Start Auto-Tuning over again and enter the correct information.
The wiring is faulty. Check the wiring and correct defective connections.
Check around the machine.
Check the load.
Load is too heavy.
Er-03 STOP Button Input
Cause Possible Solutions
Auto-Tuning canceled by
pressing STOP button.
Auto-Tuning did not complete properly and will have to be performed again.
Er-04 Line-to-Line Resistance Error
Cause Possible Solutions
Motor data entered during
Auto-Tuning was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the
correct data.
Start Auto-Tuning over again and enter the correct information.
Auto-Tuning did not complete
within designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Rotational Auto-Tuning.
Drive-calculated values outside
parameter setting range.
Er-05 No-Load Current Error
Cause Possible Solutions
Motor data entered during
Auto-Tuning was incorrect.
Motor data entered to T1 parameters does not match motor nameplate. Enter the
correct data.
Restart Auto-Tuning and enter the correct information.
Auto-Tuning did not complete
within designated time frame.
Check and correct faulty motor wiring.
Disconnect the motor from machine and perform Rotational Auto-Tuning.
Drive-calculated values outside
parameter setting range.
Er-08 Rated Slip Error
5.5 Auto-Tuning Fault Detection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
151
5
Troubleshooting

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20