H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function Description
13 Speed Agree 2
Closed: When drive output frequency equals the frequency reference +/-
L4-04.
14 User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03
(plus or minus L4-04).
15 Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value
in L4-03 with the hysteresis determined by L4-04.
16 Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value
in L4-03 with the hysteresis determined by L4-04.
17 Torque Detection 1 (N.C.)
Open: When the output current/torque exceeds the value set in parameter
L6-02 for more time than is set in parameter L6-03.
18 Torque Detection 2 (N.O.)
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
19 Torque Detection 2 (N.C.)
Open: Output current/torque exceeds the value set in parameter L6-05
for more time than is set in parameter L6-06.
1A During Reverse Operation Closed: Drive is running in the reverse direction.
1B During Baseblock (N.C.) Open: Drive is in base block condition. Output is disabled.
1C Motor 2 Selection
Closed: Motor 2 is selected by a digital input (H1-oo = 16)
1E Restart Enabled Closed: An automatic restart is performed
1F Motor Overload Alarm (oL1) Closed: OL1 is at 90% of its trip point or greater.
20 Drive Overheat Pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value.
22 Mechanical Weakening Closed: Mechanical Weakening detected.
2F Maintenance Period
Closed: cooling fan, electrolytic capacitors, IGBTs, or the soft charge
bypass relay may require maintenance.
Note: Available in drive software versions PRG: 1016 and later.
30 During Torque Limit Closed: When the torque limit has been reached.
37 During Frequency Output
Closed: Frequency is output
Open: Operation stopped, Baseblock, DC Injection Braking, or Initial
Excitation is being performed.
38 Drive Enable
Closed: Multi-function input closes (H1-oo = 6A)
39 Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for each
incremented kWh count.
3C LOCAL/REMOTE Status
Closed: LOCAL
Open: REMOTE
3D During Speed Search Closed: Speed search is being executed.
3E PID Feedback Low Closed: PID Feedback Loss.
3F PID Feedback High Closed: PID Feedback Fault.
4A During KEB Operation Closed: KEB is being performed.
4B During Short-Circuit Brake Closed: Short-Circuit Braking is active.