75
IM 01B08B02-01EN
List of Parameters
List of Parameters
Configuration Display 2 (CONFIG2)
Parameter Name Setting and Display Range Unit
Factory Default Value
Display and Setting Conditions
for Controller Mode
User
Set-
tings
YS1500
(SINGLE)
YS1700
(PROG)
SINGLE CAS
SELECT
PROG
SET Enable/Disable setting INHB: Setting impossible ENBL: Setting possible (Note1) INHB R/W R/W R/W R/W
CMOD1 C-mode 1 -: None, CAS: Analog cascade setting mode, CMP: Computer cascade setting mode - R/W R/W R/W R/W
BMOD1 Backup mode 1 BUM: Manual operation backup mode, BUA: Automatic operation backup mode BUM R/W R/W R/W R/W
CNT1 Control type 1
PID: Standard PID (Note 2), S-PI: Sample-and-hold PI control (Note 2),
BATCH: Batch PID control (Note 2), PD: Proportional (PD) control (Note 2)
PID R/W R/W R/W R/W
ALG1 Control operation formula 1 I-PD: PV proportional type PID, PI-D: PV derivative type PID, SVF: Adjustable setpoint filter I-PD R/W R/W R/W R/W
ACT1 Control operation direction 1 RVS: Reverse action DIR: Direct action RVS R/W R/W R/W R/W
VDIR1 Valve direction 1 C-O: MV 0%=Close, 100%=Open, O-C: MV 0%=Open, 100%=Close C-O R/W R/W R/W R/W
SCH1 100% value of scale 1 -80000 to 80000 1000 R/W R/W R/W R/W
SCL1 0% value of scale 1 -80000 to 80000 0 R/W R/W R/W R/W
SCDP1 Decimal point position 1 #####, ####.#, ###.##, ##.###, #.#### ####.# R/W R/W R/W R/W
SCDV1 Scale division 1 1, 2, 4, 5, 7, 10, 14, 20 10 R/W R/W R/W R/W
UNIT1 Engineering unit 1 Alphanumeric character 7 digits % R/W R/W R/W R/W
TAG1 Tag number 1 Alphanumeric character 12 digits
---YS1500--- ---YS1700---
R/W R/W R/W R/W
CMOD2 C-mode 2 -: None, CAS: Analog cascade setting mode, CMP: Computer cascade setting mode - N/A N/A R/W R/W
BMOD2 Backup mode 2 BUM: Manual operation backup, BUA: Automatic operation backup BUM N/A N/A N/A R/W
CNT2 Control type 2
PID: Standard PID (Note 2), S-PI: Sample-and-hold PI control (Note 2),
BATCH: Batch PID control (Note 2), PD: Proportional (PD) control (Note 2)
PID N/A R/W R/W R/W
ALG2 Control operation formula 2 I-PD: PV proportional type PID, PI-D: PV derivative type PID, SVF: Adjustable setpoint filter I-PD N/A R/W R/W R/W
ACT2 Control operation direction 2 RVS: Reverse action DIR: Direct action RVS N/A R/W R/W R/W
VDIR2 Valve direction 2 C-O: MV 0%=Close, 100%=Open, O-C: MV 0%=Open, 100%=Close C-O N/A N/A N/A R/W
SCH2 100% value of scale 2 -80000 to 80000 1000 N/A R/W R/W R/W
SCL2 0% value of scale 2 -80000 to 80000 0 N/A R/W R/W R/W
SCDP2 Decimal point position 2 #####, ####.#, ###.##, ##.###, #.#### ####.# N/A R/W R/W R/W
SCDV2 Scale division 2 1, 2, 4, 5, 7, 10, 14, 20 10 N/A R/W R/W R/W
UNIT2 Engineering unit 2 Alphanumeric character 7 digits % N/A R/W R/W R/W
TAG2 Tag number 2 Alphanumeric character 12 digits
---YS1700---
N/A R/W R/W R/W
Note 1: When the SET parameter is set to “ENBL”, [STOP] will appear on the right of the display title, and the manipulated output and alarm output will be kept.
Note 2: In the single-loop mode, “PID”, “S-PI” or “PD” is available for setting. In the cascade mode, “PID” or “S-PI” is available for setting. In the selector mode, “PID” is available for setting. “BATCH” is for programmable
mode.
Be sure to set the ALG1 and ALG2 (Control operation formula 1, 2) to “PI-D”. The same settings should be done to each control module (basic/cascade/selector control) used in the programmable mode.