34 ProCapture-T & PRoRF-T User Manual
the state of the door sensor is inconsistent with that of the door sensor mode, alarm will be triggered.
The time period is the Door Sensor Delay (value ranges from 1 to 255 seconds).
Door Sensor Type: It includes None, Normal Open (NO) and Normal Close (NC). None means door
sensor is not in use; Normal Open means the door is opened when electricity is on; Normal Close
means the door is closed when electricity is on.
Verification Mode: Select verification mode to open door, including password / fingerprint / badge,
fingerprint only, user ID only, password, badge only, fingerprint / password, fingerprint / badge, password
/ badge, user ID & fingerprint, fingerprint & password, fingerprint & badge, fingerprint & password &
badge, password & badge, user ID & fingerprint & password, fingerprint & badge & user ID.
Remarks:
1. “/” means “or”. “&” means “and”.
2. In a combined verification mode, the corresponding verification information must be registered
first. For example: When User A registers fingerprint only, and the [Verification Mode] is set as
“Password & Badge”, User A will not pass verification.
Door Available Time Period: Set periods to open the door for users.
NO Time Period: To set time period for Normally Open, so that the door is always unlocked during this
period.
Use as master: While configuring the master and slave devices, you may set the state of the master as
Out or In.
Out: A record of verification on the master device is a check-out record.
In: A record of verification on the master device is a check-in record.
Auxiliary Input Configuration: To set the Aux output/lock open time and Aux Output type for the
device with auxiliary connector. Aux Output type includes None, trigger door open, trigger Alarm,