Parameters 115
06.22 Hand-off-auto
status word
ACQ580 specific status word.
This parameter is read-only.
-
0000h…FFFFh Start inhibit status word. 1 = 1
06.30 MSW bit 11
selection
Selects a binary source whose status is transmitted as bit 11
(User bit 0) of 06.11 Main status word.
Ext ctrl loc
False 0. 0
True 1. 1
Ext ctrl loc Bit 11 of 06.01 Main control word (see page 111). 2
Other [bit] Source selection (see Terms and abbreviations on page 100). -
06.31 MSW bit 12
selection
Selects a binary source whose status is transmitted as bit 12
(User bit 1) of 06.11 Main status word.
Run
permissive
False 0. 0
True 1. 1
Run permissive Status of the external run permissive signal (see parameter
20.40 Run permissive).
3
Other [bit] Source selection (see Terms and abbreviations on page 100). -
06.32 MSW bit 13
selection
Selects a binary source whose status is transmitted as bit 13
(User bit 2) of 06.11 Main status word.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 100). -
06.33 MSW bit 14
selection
Selects a binary source whose status is transmitted as bit 14
(User bit 3) of 06.11 Main status word.
False
False 0. 0
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Hand mode 0 = Drive is not operated from the panel in the Hand mode; 1 =
Drive is operated from the panel in the Hand mode
1 Off mode 0 = Drive is not in the Off mode; 1 = Drive is in the Off mode.
2 Auto mode 0 = Drive is not in the Auto mode; 1 = Drive is in the Auto mode.
3 Reserved
4 Pre-heating 0 = Motor pre-heating is not active; 1 = Motor pre-heating is
active.
5 Damper control 0 = Damper control is not active; 1 = Damper control is active.
6 Reserved
7 Run permissive 0 = Run permissive is not present, drive is not allowed to run; 1 =
Run permissive is present, drive is allowed to run.
8 Start interlock 1 0 = Start interlock 1 is not present, drive is not allowed to start;
1 = Start interlock 1 is present, drive is allowed to start.
9 Start interlock 2 0 = Start interlock 2 is not present, drive is not allowed to start;
1 = Start interlock 2 is present, drive is allowed to start.
10 Start interlock 3 0 = Start interlock 3 is not present, drive is not allowed to start;
1 = Start interlock 3 is present, drive is allowed to start.
11 Start interlock 4 0 = Start interlock 4 is not present, drive is not allowed to start;
1 = Start interlock 4 is present, drive is allowed to start.
12…15 Reserved