Parameters 119
10.23 RO forced data Contains the values of relay outputs that are used instead of
the connected signals if selected in parameter 10.22 RO
force selection. Bit 0 is the forced value for RO1.
0000h…FFFFh Forced RO values. 1 = 1
10.24 RO1 source Selects a drive signal to be connected to relay output RO1. Ready run
Not energized Output is not energized. 0
Energized Output is energized. 1
Ready run Bit 1 of 06.11 Main status word (see page 111). 2
Enabled Bit 0 of 06.16 Drive status word 1 (see page 112 ). 4
Started Bit 5 of 06.16 Drive status word 1 (see page 112 ). 5
Magnetized Bit 1 of 06.17 Drive status word 2 (see page 112 ). 6
Running Bit 6 of 06.16 Drive status word 1 (see page 112). 7
Ready ref Bit 2 of 06.11 Main status word (see page 111). 8
At setpoint Bit 8 of 06.11 Main status word (see page 111). 9
Reverse Bit 2 of 06.19 Speed control status word (see page 113). 10
Zero speed Bit 0 of 06.19 Speed control status word (see page 113). 11
Above limit Bit 10 of 06.17 Drive status word 2 (see page 11 2). 12
Warning Bit 7 of 06.11 Main status word (see page 111). 13
Fault Bit 3 of 06.11 Main status word (see page 111). 14
Fault (-1) Inverted bit 3 of 06.11 Main status word (see page
111). 15
Fault/Warning Bit 3 of 06.11 Main status word OR bit 7 of 06.11 Main status
word (see page 111).
16
Overcurrent Fault 2310 Overcurrent has occurred. 17
Overvoltage Fault 3210 DC link overvoltage has occurred. 18
Drive temp Fault 2381 IGBT overload or 4110 Control board temperature
or 4210 IGBT overtemperature or 4290 Cooling or 42F1 IGBT
temperature or 4310 Excess temperature or 4380 Excess
temperature difference has occurred.
19
Undervoltage Fault 3220 DC link undervoltage has occurred. 20
Motor temp Fault 4981 External temperature 1 or 4982 External
temperature 2 has occurred.
21
Reserved 22
Ext2 active Bit 11 of 06.16 Drive status word 1 (see page 112 ). 23
Remote control Bit 9 of 06.11 Main status word (see page 111). 24
Reserved 25…26
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 27
Timed function 2 Bit 1 of 34.01
Timed functions status (see page 191). 28
No. Name/Value Description Def/FbEq16
Bit Value
0 Force the value of this bit to RO1, if so defined in parameter 10.22 RO force selection.
1 Force the value of this bit to RO2, if so defined in parameter 10.22 RO force selection.
2 Force the value of this bit to RO3, if so defined in parameter 10.22 RO force selection.
3…15 Reserved