Parameters 143
In1P Start; In2 Stop The sources of the start and stop commands are selected by
parameters 20.03 Ext1 in1 source and 20.04 Ext1 in2 source.
The state transitions of the source bits are interpreted as
follows:
Notes:
Parameter 20.02 Ext1 start trigger type has no effect with
this setting.
When source 2 is 0, the Start and Stop keys on the control
panel are disabled.
4
Reserved 5…10
Control panel The start and stop commands are taken from the control
panel (or PC connected to the panel connector).
Note: This selection requires ACS-AP-I panel that uses
Start/Stop/Loc/Rem logic.
11
Fieldbus A The start and stop commands are taken from fieldbus adapter
A.
Note: Set also 20.02 Ext1 start trigger type to Level.
12
Reserved 13
Embedded fieldbus The start and stop commands are taken from the embedded
fieldbus interface.
Note: Set also 20.02 Ext1 start trigger type to Level.
14
20.02 Ext1 start trigger
type
Defines whether the start signal for external control location
EXT1 is edge-triggered or level-triggered.
Note: This parameter is not effective if a pulse-type start
signal is selected. See the descriptions of the selections of
parameter 20.01 Ext1 commands.
Level
Edge The start signal is edge-triggered. 0
Level The start signal is level-triggered. 1
20.03 Ext1 in1 source Selects source 1 for parameter 20.01 Ext1 commands. DI1
Not selected 0 (always off). 0
Selected 1 (always on). 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02
DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 24
No. Name/Value Description Def/FbEq16
State of source 1
(20.03)
State of source 2
(20.04)
Command
0
-
> 1 1 Start
Any 0 Stop

Table of Contents