146 Parameters
-DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 9
-DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 10
-DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 11
-DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 12
-DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 13
Fieldbus adapter This selection cannot be used to control Start interlock with
ABB drives profile from the fieldbus adapter. Use Other [bit]
and map to control word user bits.
14
Embedded fieldbus Start interlock 1: DCU profile: Inverse of control word bit 18
received through the embedded fieldbus interface.
Start interlock 2: Inverse of bit 19.
15
Other [bit] Source selection (see Terms and abbreviations on page 100). -
20.42 Start interlock 2 Selects the source of the Start interlock 2 signal.
For the selections, see parameter 20.41 Start interlock 1.
Selected
20.43 Start interlock 3 Selects the source of the Start interlock 3 signal.
For the selections, see parameter 20.41 Start interlock 1.
Selected
20.44 Start interlock 4 Selects the source of the Start interlock 4 signal.
For the selections, see parameter 20.41 Start interlock 1.
Selected
20.45 Start interlock stop
mode
Selects the method of stopping if a Start interlock signal is
lost. Applies to 20.41 Start interlock 1, 20.42 Start interlock 2,
20.43 Start interlock 3 and 20.44 Start interlock 4.
Not used
Not used Not in use. 0
Coast The motor coasts to a stop. 1
Ramp Stop along the active deceleration ramp. 2
20.46 Run permissive text Alternative alarm texts for the run permissive. Run
permissive
Run permissive 0
Valve opening 2
Pre-lube cycle 3
20.47 Start interlock 1 text Alternative alarm texts for the start interlock 1. Start
interlock 1
Start interlock 1 0
Vibration switch 1
Firestat 2
Freeze stat 3
Overpressure 4
Vibration trip 5
Smoke alarm 6
Auxiliary open 7
Low suction 8
Low pressure 9
Access door 10
Pressure relief 11
Motor disconnect
open
12
No. Name/Value Description Def/FbEq16